儀表伴熱(re)電纜安裝的詳細說(shuo)明
伴熱(re)(re)(re)電(dian)(dian)(dian)纜(lan)應按管(guan)道長(chang)(chang)(chang)度分布(bu),以免(mian)管(guan)內(nei)介質在無(wu)伴熱(re)(re)(re)電(dian)(dian)(dian)纜(lan)處(chu)降(jiang)溫凝結,伴熱(re)(re)(re)電(dian)(dian)(dian)纜(lan)的長(chang)(chang)(chang)度應長(chang)(chang)(chang)于(yu)被伴熱(re)(re)(re)管(guan)道。安(an)(an)裝時(shi)應效驗(yan)所用(yong)(yong)伴熱(re)(re)(re)電(dian)(dian)(dian)纜(lan)長(chang)(chang)(chang)度(包括(kuo)并聯(lian)的各分支總長(chang)(chang)(chang)度),是否超(chao)(chao)過設(she)計長(chang)(chang)(chang)度或允(yun)許的最大使用(yong)(yong)長(chang)(chang)(chang)度。敷設(she)時(shi)應盡(jin)可能使伴熱(re)(re)(re)電(dian)(dian)(dian)纜(lan)平整地(di)緊貼在管(guan)道表面(mian),應采用(yong)(yong)鋁箔膠(jiao)帶(dai)黏貼,一則增大散熱(re)(re)(re)面(mian)積,有利于(yu)熱(re)(re)(re)傳導﹔二則方(fang)便安(an)(an)裝。其方(fang)法(fa)是:先清(qing)除伴熱(re)(re)(re)電(dian)(dian)(dian)纜(lan)途徑(jing)處(chu)的油污、水分,每隔30厘(li)米(最大不超(chao)(chao)過80厘(li)米)用(yong)(yong)耐熱(re)(re)(re)壓(ya)(ya)敏膠(jiao)帶(dai)將徑(jing)向固(gu)定,然后敷設(she)覆(fu)蓋鋁箔膠(jiao)帶(dai),最后用(yong)(yong)布(bu)用(yong)(yong)力抹壓(ya)(ya),使伴熱(re)(re)(re)電(dian)(dian)(dian)纜(lan)平整地(di)貼在導壓(ya)(ya)管(guan)表面(mian)。
安裝完成后(hou),需(xu)對每根伴熱電纜(lan)進行絕緣測(ce)試。用(yong)1000V兆歐(ou)表測(ce)試伴熱電纜(lan)導電芯線與其金屬屏蔽層和導壓管間的絕緣電阻,其值不小于(yu)20MQ,否則(ze),應(ying)找出原因,排(pai)除故(gu)障。測(ce)試結果應(ying)記(ji)錄(lu)備查。
(此(ci)伴熱電(dian)纜安(an)裝為某(mou)工程的節選(xuan),僅供參考)
1、伴熱電纜的纏繞必須繞過儀表介(jie)質進口的底部。
2、伴(ban)熱電(dian)纜(lan)(lan)進(jin)接線端必須留有幅(fu)度(du),防止水順著電(dian)纜(lan)(lan)進(jin)接線盒(he)。
3、伴熱電纜末端(duan)禁止短接,可剪v字(zi)型纏絕緣膠帶可有效(xiao)避免短接。
4、儀表底座的(de)排空處不需要保溫伴熱。
5、伴熱電纜(lan)在接近取源口的地方可以纏(chan)繞幾圈做預留。
6、接線盒內(nei)(nei)的地線絕緣(yuan)要做好,盒內(nei)(nei)空間小容易對地。特(te)別(bie)是差(cha)壓(ya)變送器有⒉根(gen)伴熱電纜在一個盒子里接線。
7、安裝(zhuang)時(shi)(shi)應防(fang)止割破(po)伴熱電纜護套,固定外層保溫鐵皮(pi)時(shi)(shi)螺釘不得過(guo)長,以免刺破(po)護套。
上一篇:電伴熱帶全網最詳細安裝教程
下一篇:伴熱電纜功率越高越好嗎